STEAM AND CONDENSATE AUDIT
Project N°30275
Date: 04/02/2011
GSK MANUFACTURING Aranda, Spain
Page 38 of 45
Established by E. Morin
To the attention of Ms. Beatriz Herrero-Gonzalo
3. Radiation losses Boiler capacity
3,1 ton/h (=2MW)
Load
32 %
0,2 %
Radiation losses at full load
Radiation losses
4,1 kW
-0,6%
4. Blow down TDS Make-up water
50,0 ppm
1520,0 ppm
TDS Feed water boiler
Boiler water lost by blow down + carry over
3,4 % of steam output (30,4cycles)
1,319 ton/h
Boiler feed water flow
Boiler water lost by blow down + carry over
0,043 ton/h
1,000
X-value of the steam from the boiler
Blow down flow remaining
0,043 ton/h
Enthalpy blow down water
721 kJ/kg
12,0 °C
Temperature make up water
Enthalpy make up water
50,2 kJ/kg
Total Blow Down losses (Boiler + Deaerator)
8,1 kW
-1,3%
Blow down losses compensated by boiler only
4,0 kW
-0,6%
5. Energy losses due to excess of water Feed water tank pressure
0,0 bar(g)
% of revaporisation (7 to 0 barg)
13,5%
Water excess
40,0 %
1,319 ton/h
Feed water flow
Condensate flow out of separator
0,484 ton/h
Condensate enthalpy
721 kJ/kg
12,0 °C
Temperature make up water
Enthalpy make up water
50,2 kJ/kg
Flash steam flow
0,066 ton/h
Energy loss from condensate
44,7 kW
-6,9%
6. Boiler Efficiency and Fuel Costs Net power output in steam from the boiler
556,4 kW ( 3472 MWh)
86,0%
Net steam production boiler
0,791 ton/h = 4938 t/year
Boiler efficiency on LHV
86,05 %
BOILERHOUSE SIMULATION
Boiler house operating hours
6.240 hours/year
6. Steam consumption feed water tank
% LHV
0,29 m3/h
Measured make up water flow
Enthalpy make-up water
50,16 kJ/kg
Feed water flow to boilers
1,32 m3/hr
Enthalpy feed water
388,74 kJ/kg
Enthalpy condensate from separator (liquid phasis)
712,30 kJ/kg
Enthalpy flash steam from condensate (separator)
2259,04 kJ/kg
Made with FlippingBook Digital Publishing Software