Clayton Armstrong 2011-02-22 GSK Aranda SP - steam&condensat
STEAM AND CONDENSATE AUDIT
Project N°30275
Date: 04/02/2011
GSK MANUFACTURING Aranda, Spain
Page 45 of 45
Established by E. Morin
To the attention of Ms. Beatriz Herrero-Gonzalo
11.3 Savings
The installation of closed loop pumping trap systems, or a Posipressure system, will return
condensate back to the boiler house. Often on flooded heat exchangers this condensate is drained
to sewer and therefore lost. It can increase the heat exchangers capacity, and may speed up
production processes. More important are the savings achieved from improved system reliability
and controllability, however these are often difficult to quantify. The safety drain will not improve the
condensate return, but will save the coil from freezing and prevent process time downs and
maintenance labour to repair.
11.4 Investments
Average budgetary cost for the installation of a closed loop pumping trap system on an existing heat
exchanger is 14000 €.
Average budgetary cost for the installation of a Posipressure system on an existing heat exchanger
is 8000 €.
Average budgetary cost for the installation of a Safety Drain on an existing heat exchanger is 1700€.
Included:
- Equipments supply (piping, pumping trap / Posipressure, valves etc. )
- Installation by a mechanical contractor
- Engineering and project management
Payback time for these optimizations depends on the specific situation.