STEAM AND CONDENSATE AUDIT
Project N°30275
Date: 04/02/2011
GSK MANUFACTURING Aranda, Spain
Page 10 of 45
Established by E. Morin
To the attention of Ms. Beatriz Herrero-Gonzalo
According to your water analysis, TDS concentration is half of the lowest value recommended by
Clayton. Therefore you could reduce at least by 2 the blowdown rate.
The easiest solution is to change the duration of blowdown valves opening defined in the BMS
system. In agreement with Nalco, you can reduce the blowdown duration to 2 minutes every 2 hours
for example.
Another solution consists in installing a TDS probe on the feedwater line and control the blowdown
valve continuously.
3.3 Savings calculation
Reduce Blowdown rate
Existing
Proposed
Savings
Make-up water TDS
ppm
50,0
50,0
Feedwater TDS
ppm
1520,0
3000,0
Blowdown rate
%
3,40
1,69
1,71
Water savings
Existing
Proposed
Savings
Steam production of the boiler
kg/h
1000,0
1000,0
Blowdown flow
kg/h
34,0
16,9
17,1