2000 Hook-up Book
Figure II-100 Control Panel Hook-up and Operation of Two Valve Blowdown VRS-2 Rotary Filter System
Figure II-100A
Figure II-100B
Motor Wiring
Motor Wiring
Outlet Pressure Line
Outlet Pressure Line
Inlet Pressure Line
Inlet Pressure Line
P 2
P 2
P 1
P 1
Model VRS-2 Rotary Filter
Model VRS-2 Rotary Filter
Model VRS Control Panel
Model VRS Control Panel
Main Power
Main Power
CV 1
CV 1
D.P. Switch
D.P. Switch
Valve Wiring
Valve Wiring
Reservoir Pipe
Reservoir Pipe
Full Port Quarter Turn Motorized Valve
Full Port Quarter Turn Motorized Valve
CV 2
CV 2
HOOK-UP DIAGRAMS
Removed Solids
Removes Solids
the reservoir pipe fills, valve CV 1 closes and valve CV 2 opens purging only material held in the reservoir leg, Fig. II-100B. CV 2 closes and CV 1 reopens returning system to normal running mode with no stoppage of
flow. This hook-up illustrates an auto matic filtration system, providing continuous product flow with virtually no loss of usable fluid.
Figure II-101 Motorized Rotary Filter with Three Valve Blowdown System for Viscous FLuids The Control Panel operates rotor and blowddown valves CV 1 and CV 2 automatically. Fig. II-100A shows the normal running mode with CV 1 valve open and CV 2 valve closed, to allow reservoir to fill with dirt and debris. As
Motor Wiring
Outlet Pressure Line
P 1
P 2
Inlet Pressure Line
Model VRS-2 Rotary Filter
Model VRS Control Panel
Main Power
CV 3
CV 1
D.P. Switch
High Pressure Purge
Full Port Quarter Turn Motorized Valves
See Fig. II-100A and II 100B for sequence of operation. In addition to the blowdown valves on the reservoir pipe, a third valve CV 3 has been added for a high pressure purge fluid or air should the debris in the reservoir pipe prove to be too viscous to flow by gravity.
Reservoir Pipe
Valve Wiring
CV 2
Removed Solids
134