2000 Hook-up Book
HOOK-UP DIAGRAMS Figure II-102 Freeze Proof Safety Shower with Antiscalding Protection a a Figure II-103 Automatic Contol of Smaller Compressor Cooling with Overheat Protection The T-44 control valve incorporates a bypass needle valve to keep a min imum flow of water past the sensor even when the main valve has closed. A float-type drainer is preferred for the separator rather than a TD drainer, to ensure immediate and complete drainage of the separated liquid. Larger compressors or low pressure cooling water supplies may call for a separate supply of water to the aftercooler, with a solenoid valve or similar, to open when the compressor runs. Fit T-44 control (with bypass closed), 85˚F to 135˚F range, in 1 1/4” or larger pipe. Flow crosses sensor to shower, to cooling valve inlet ending at the #8 that opens when ambient drops below 40°F. Line flow prevents both freeze up and solar over heating. Drain Strainer Liquid Drain Trap Air Line Moisture Separator Strainer Cooling Control Float Operated Air Vent Cooling Water Warmed Coolant Compressor Jacket After Cooler Water Supply #8 set @ 40°F Strainer Cooling Control Spring Closed Valve To Shower Head Overheat Drain