R020932J1, Install Manual
Section I I I
Table 3-2: Hotwell (Open) and Deaerator Systems
DA ONLY
Customer Connections
Booster Pump(s)
Water Softener(s)
Blowdown Tank
Cooling Water Inlet
Safety Valve Out
BPR Outlet
PRV Inlet
Skid Type
Inlet Outlet Recirc Inlet Outlet Drain Inlet Outlet Vent
None
X X X X X X X X X X X X X
Condensate Skid
X
X X X X X X X X X X
Water Skid
X X
X X
X X X X
X X X X X X
Generator Skid
3.4 OPEN SYSTEM
(Refer to P&ID drawing R-19477.) In an open system, the makeup water, condensate returns (system and separator trap returns), chemi- cal treatment, and heating steam are blended in an atmospheric feedwater receiver tank, (vented to atmo- sphere - under no pressure). Open feedwater receiver systems are sized to provide the necessary volume of feedwater and sufficient retention time for the chemical treatment to react. Condensate, separator trap returns and feedwater treatment chemicals are injected at the opposite end of the tank as the feedwater outlet connection. This helps to avoid potential feedwater delivery problems to the booster or feedwater pump(s), and to provide sufficient reaction time for the chemical treatment. Installation guidelines for the feedwater receiver are provided below. Descriptions for the other water treatment and accessory components, shown in R-19477, are provided in Section VII (Optional Equip- ment) and/or in the Clayton Feedwater Treatment Manual.
NOTE All piping to and from the feedwater receiver must remain the same or larger size as the tank connection and not reduced. See Table 3-3 below for connec- tion requirements.
3-3
07/10/2015