STEAM AND CONDENSATE AUDIT
Project N°30275
Date: 04/02/2011
GSK MANUFACTURING Aranda, Spain
Page 24 of 45
Established by E. Morin
To the attention of Ms. Beatriz Herrero-Gonzalo
6 Optimisation project n°4: Replace failed steam traps
6.1 Current situation
A full trap survey was done during our audit. There are 98 steam traps identified and listed on your
steam system drawings. 15 of the installed traps were failing (13 leaking, 2 plugged) and 34 could
not be tested as the units were out of service.
The details of the trap survey and its results are available on SteamStar trap management online
platform.
Here are the access parameters of this trap survey:
Login : beatriz.herrero@gsk.com
Full Name : Beatriz Herrero Gonzalo
Password : B34Tr1ZH3Rr3
Website : www.steamstar.com
Summary of results: