Clayton Armstrong 2011-02-22 GSK Aranda SP - steam&condensat
STEAM AND CONDENSATE AUDIT
Project N°30275
Date: 04/02/2011
GSK MANUFACTURING Aranda, Spain
Page 21 of 45
Established by E. Morin
To the attention of Ms. Beatriz Herrero-Gonzalo
5 Optimisation project n°3: Improve steam ancillaries insulation
5.1 Current situation
Not only for safety reason, must hot surfaces have effective insulation to
prevent excessive heat loss by radiation. The basic function of insulation
is to retard the flow of unwanted heat transfer. There is more chance of
part of steam to condense during distribution if the pipelines are not
properly insulated.
There is a closely interrelated efficiency between boilers and their
distribution systems. The losses occurred in the distribution systems have
a significant impact on boiler operations. When these losses are minimized, boiler plant efficiency is
improved.
We observed some valves and filters on steam lines which are not insulated in your steam
distribution system.
The following table shows the non-insulated equipments identified during the audit:
Location
Ancillaries length or
DN
Pressure
loss
type
number
(mm)
(barg)
(W)
Boiler house (Eagle)
Back Pressure valves
valve
2
80
7
2106
Eagle building
2nd floor South
valve
2
100
7
2796
Pressure Reducing Station
strainer
1
100
7
1398
Pressure Reducing Station
valve
1
100
4
1137
GLATT 6115
valve
2
32
4
745
2nd Floor North Lavado
valve
1
32
4
373
2nd Floor North Lavado
valve
1
40
4
425
4th floor south
valve
3
40
2
1069
4th floor south
strainer
1
40
2
356
Tunnel 2 aera
1st floor VP37
valve
1
50
6
618