Section I I - General Information
Exhaust stacks are to be self-supporting (maximum stack connection load is 50 lbs. {22 kg}) and must extend well above the roof or building, (refer to local building codes). If nearby structures are higher than the building housing the steam generator(s), the stack height should be increased to clear these struc- tures.
NOTE It is strongly recommended that a back draft damper (full size and motor operated with position interlock switch) be installed to prevent freeze damage to the heating coil. Machine installations, in cold weather zones, that plan to lay the machine up wet and may encounter freezing conditions must install an air-tight back draft damper in the exhaust stack to prevent down-draft freezing.
Clayton recommends insulating all exhaust stacks to maintain gas temperatures above dew point.
Special consideration should be given to installations in and around residential areas. Depending on the design, some noise and harmonic vibration may emanate from the exhaust stack. The noise/harmonics may bounce off surrounding structures and be offensive to employees and neighbors. If this condition occurs, a stack muffler is recommended. In-line stack mufflers are typically used, installed vertically and above roof level. They may be installed horizontally or closer to the equipment. See Figures 2-2, 2-3, and 2-4 for stack configurations.