Heat Recovery Systems

THE CLAYTON HOT WATER SYSTEM

TEMPERATURE REGULATOR

WATER OUT

TC

SECONDARY WATER OUT

HEAT CONSUMER

EXPANSION TANK

SECONDARY WATER IN

WATER IN

EXHAUST GAS BOILER

CIRCULATION PUMP

gas combustion, from a diesel engine or spark ignited engine, gasses containing traces of soot and unburned lubricating oil. The primary loop contains a circulating pump, expansion vessel and heat exchanger(s) with control valve(s).

The Clayton exhaust gas boiler can also be used in a closed loop generating hot water. The temperature level of the water depends on the type of fuel. The miminum temperature for the water to enter the boiler however is generally as follows : -130° C for heavy fuel oils - 95°C for diesel fuel oils - 70°C for gasses coming froma natural gas combustion, clean gas - 95°C for gasses coming from a natural

16

Made with FlippingBook Digital Publishing Software