Boletin 274 SMOKE SAMPLER USED IN ALL EQUIPMENT

Esta publicación interactiva se ha creado por Clayton de México S.A. de C.V.

BULLETIN

274

Manufacturing Engineering

Month: February

Year : 2024

SMOKE SAMPLER USED IN ALL EQUIPMENT

I hereby inform you that the smoke samplers that we use in our equipment will no longer be supplied on the parts lists. This change is due to the fact that NOM-085-SEMARNAT-2011 does not require carrying out the test before any air infiltration, this indication was eliminated from the standard, therefore we will stop using the sampler, the combustion gas intake test by part of our technicians must be carried out on the couplings placed around the chimney thermometer, the installations area will place another coupling to perform the test. It should be remembered that the smoke shadow test is mandatory for all equipment, both diesel and gas. The values assigned to consider the carburetion tests will continue to be recorded as they have been doing, the values shown in the table are only for Clayton equipment and the equipment must be in accordance with the indicated values. The table attached to this bulletin HAS NO OFFICIAL VALIDITY , therefore it is necessary to coordinate with the verification unit to preserve the values that they indicate. All analyzes must be available for review by the environmental authority. The client must keep a log of the fixed sources referred to in this Official Mexican Standard for the operation and maintenance of equipment, whether in written or electronic format. The log must be available for review by the environmental authority and must contain at least the following information: Name, brand and nominal thermal capacity of the combustion equipment(s), and if it has emission control and pollutant measurement equipment, its name and brand. In the daily records you will note:

• Date. • Shift. • Consumption and type of fuel. • Percentage of the design capacity at which the equipment operated. • Average temperature of the chimney gases.

All data obtained from the carburetion of each of the equipment must be recorded in the visit order. In the visit order they must add the impression of the smoke shadow, indicating the degree of opacity.

REVISION DEL FORMATO: D

FECHA DE EFECTIVIDAD DEL FORMATO:23/06/2023

EMISSIONS THAT STEAM GENERATORS AND HOT WATER GENERATORS MUST HAVE TO COMPLY WITH THE NOM-085-ECOL-2011 STANDARD

EO10 EO15 EO20

EG10 EG15 EG20

EO30 EO40 TO1400

EO100 SFO100S SFO100M TO5000

EG100 SFG100S SFG100M TG5000

EG30 EG40 TG1400

EO150 SFO150S SFO150M

EG150 SFG150S SFG150M

EO185 SFO200S SFO200M

EG185 SFG200S SFG200M

EO60 TO2500

EG60 TG2500

MODELS

TO500 TO700

TG500 TG700

Carbon Monoxide (CO), Maximum

ppm

150

100

150

100

150

100

150

100

150

100

150

100

Carbon Dioxide (CO2),

%

10.4-12 8.2-9.9

10.4-12

8.2-9.9 10.4-12

8.2-9.9

10.4-12

8.2-9.9

10.4-12

8.2-9.9

10.4-12

8.2-9.9

Nitrogen Oxides (NOx)

ppm

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

100

100

Excess Air

%

20-40

20-35

20-40

20-35

20-40

20-35

20-40

20-35

20-40

20-35

20-40

20-35

Oxygen

%

4-6

4-6

4-6

4-6

4-6

4-6

4-6

4-6

4-6

4-6

4-6

4-6

Chimney Temperature

°C

220

220

220

220

220

220

220

220

220

220

220

220

Smoke Shadow

0-2

NA

0-2

NA

0-2

NA

0-2

NA

0-2

NA

NA

NA

EO204 EO254

EG204 EG254

EO304 EO354

EG304 EG354

EO404 EO504

EG404 EG504

EO604 EO704

EG604 EG704

MODELOS

EO154 EG154

EO1004

EG1004

Carbon Monoxide (CO), Maximum

ppm

150

100

150

100

150

100

150

100

150

100

150

100

Carbon Dioxide (CO2),

%

10.4-12 8.2-9.9 10.4-12

8.2-9.9

10.4-12

8.2-9.9

10.4-12

8.2-9.9

10.4-12

8.2-9.9

10.4-12

8.2-9.9

Nitrogen Oxides (NOx)

ppm

100

100

100

100

100

100

100

100

100

100

100

100

Excess Air

%

20-40

20-35

20-40

20-35

20-40

20-35

20-40

20-35

20-40

20-35

20-40

20-35

Oxygen

%

4-6

4-6

4-6

4-6

4-6

4-6

4-6

4-6

4-6

4-6

4-6

4-6

Chimney Temperature

°C

220

220

220

220

220

220

220

220

220

220

220

220

Smoke Shadow

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

1 Megajoule = 238.84 kcal = 947.82 BTU

This bulletin does not cancel number 212 issued in September 2012.