2000 Hook-up Book
a Safety Valve Pressure Sensing Line Drip Pan Elbow
Figure II-14 Series Pressure Reducing Valve Station for High Turndown Rations
Pressure Sensing Line
Moisture Separator
Reduced Steam Pressure
Strainer
Strainer
Steam Supply
Pilot Operated Pressure Control Valve
Pilot Operated Pressure Control Valve
Check Valve
Strainer
Float & Thermostatic Steam Trap
Spira-tec Loss Detector
Spira-tec Loss Detector
Check Valve
HOOK-UP DIAGRAMS
Strainer
Float & Thermostatic Steam Trap
Note: Intermediate pressure takeoff requires an additional safety valve.
Figure II-15 Hook-up for Remote Operation of 25 PRM Pressure Reducing Valve
Safety Valve
5/16" Copper Tubing or 1/4" Pipe
Drip Pan Elbow
Moisture Separator
Noise Diffuser (if required)
Strainer
Steam Supply
Reduced Steam Pressure
Main Control Valve
Remote Pressure Pilot
1/2" Pipe
Check Valve
Check Valve
Check Valve
Strainer
Float & Thermostatic Steam Trap
Float & Thermostatic Steam Trap
Float & Thermostatic Steam Trap
Limit pilot to 15 ft. drop below main valve and drain all supply tubing. If pilot is mounted above main valve, pilot line drip traps can be eliminated. For longer distance an air loaded pilot should be used.