2000 Hook-up Book
Spira-tec Trap Leak Detector System for Checking Steam Traps
Figure 61
Purpose The Spira-tec Trap Leak Detector System is designed to indicate if a steam trap is leaking steam. It can be used to check any known type or make of trap while it is working. Equipment 1. Sensor chamber fitted immediately upstream of the trap (close coupled), the same size as the trap. 2. Indicator with cable. 3. Where the sensor chamber is not readily accessible, a Remote Test Point may be fitted at a convenient position, wired back through a junction to the sensor chamber. Remote Test Points for either one chamber or up to 12 chambers, are available. 4. An Automatic Remote Test Point, capable of interfacing with most Building Management Systems, is also available allowing up to 16 steam traps to be continuously scanned for steam wastage.
SYSTEM DESIGN
Sensor Chamber
Plug Tail
Wiring by Installer Junction
Remote Test Point
Indicator
Sensor Chamber
Single inaccessible steam trap checking system— Spira-tec sensor chamber, plug tail, wiring (by installer), remote test point, indicator and indicator cable.
Indicator Cable
Indicator
Basic steam trap checking system— Spira-tec sensor chamber, indicator and indicator cable.
Automatic Remote Test Point
Indicator
Multiple Remote Test Point
Continuous scanning system—Spira-tec Automatic Remote test point, sensor chambers, plug tails.
Multiple inaccessible steam trap checking system— Spira-tec sensor chambers, plug tails, wiring (by installer), remote multiple test point, indicator and indicator cable.
58
Made with FlippingBook. PDF to flipbook with ease