2000 Hook-up Book
Figure II-85 Clean Steam Drip Station
Clean Steam Supply
Sanitary Diaphragm Valve with Inlet Drain Boss
A
1:120 min.
Product/Media Line
B
Stainless Steel Thermo-Dynamic Steam Trap
Stainless Steel Ball Valve
HOOK-UP DIAGRAMS
1:120 min.
Condensate Manifold must be free draining
Install valve “ A ” close to product/media line. Close-couple valves “ A ” and “ B ”
Figure II-86 Culinary/Filtered Steam Station
Steam Filter with a 2.8 micron absolute filter element
Moisture Separator
Sanitary Check Valve
B
Plant Steam Inlet
A
Strainer with a Fine Mesh Screen
Stainless Steel Ball Valve
Stainless Steel Ball Valve
Stainless Steel Thermo-Dynamic Steam Trap
Spira-tec Loss Detector
Cooling Water Outlet
Strainer
Float & Thermostatic Steam Trap
Sample Cooler
A All piping, fittings, valves, etc. downstream of this point shall be of austenitic stainless steel and of sanitary design B Recommended position of plant steam pressure reducing valve if required Pressure gauges, fittings, valves, etc., are not shown for clarity.
Cooling Water Inlet
Cooled Sample
128