2000 Hook-up Book
a a
a Figure II-36 Low Pressure Steam Absorption Chiller Figure II-37 High Pressure Steam Absorption Chiller a a Float & Thermostatic Steam Trap Pressure Powered Pump Reservoir Pipe Thermo Dynamic Steam Trap with Integral Strainer To Condensate Return Motive Steam Supply Thermostatic Air Vent Check Valve Absorption Chiller Steam Supply (15 psig or less) To Condensate Return Motive Steam Supply Absorption Chiller Steam Supply (normally 45 psig or higher) Vent Packaged Pressure Powered Pump Thermo-Dynamic Steam Trap with Integral Strainer Note: Depending on chiller manufacturer, a steam trap may not be required or it may be supplied with the chiller. Other specialties needed may include a steam pressure reducing valve on the inlet, steam separator with trap, steam safety valve or inlet strainer. Drain to Safe Place a a
HOOK-UP DIAGRAMS
a a
a aa
a
102